1MRS758755 A
Table 405:
PDNSPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
Table 406:
PDNSPTOC Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
Min phase current
4.3.2.8
4.3.2.9
REC615 and RER615
Technical Manual
Unit
1=on
5=off
Unit
0...60000
ms
0.05...0.30
xIn

Monitored data

Table 407:
PDNSPTOC Monitored data
Name
START_DUR
RATIO_I2_I1
PDNSPTOC
Technical data
Table 408:
PDNSPTOC Technical data
Characteristic
Operation accuracy
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Suppression of harmonics
Step
Default
1=on
Step
Default
1
20
0.01
0.10
Type
Values (Range)
FLOAT32
0.00...100.00
FLOAT32
0.00...999.99
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the measured
current: f
±2% of the set value
<70 ms
Typically 40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
DFT: -50 dB at f = n × f
Section 4
Protection functions
Description
Operation Off / On
Description
Reset delay time
Minimum phase current
Unit
Description
%
Ratio of start time /
operate time
%
Measured current ratio
I2 / I1
Status
±2 Hz
n
, where n = 2, 3, 4, 5,...
n
405