Monitored Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 4
Protection functions
Parameter
Start value df/dt
Operate Tm Freq
Operate Tm df/dt
Restore start Val
Restore delay time
Table 473:
LSHDPFRQ Non group settings (Basic)
Parameter
Operation
Table 474:
LSHDPFRQ Non group settings (Advanced)
Parameter
Reset delay time
4.5.2.8
4.5.2.9
452
Values (Range)
Unit
-0.200...-0.005
xFn /s
80...200000
ms
120...200000
ms
0.800...1.200
xFn
80...200000
ms
Values (Range)
Unit
1=on
5=off
Values (Range)
Unit
0...60000
ms

Monitored data

Table 475:
LSHDPFRQ Monitored data
Name
START_DUR
LSHDPFRQ
Technical data
Table 476:
LSHDPFRQ Technical data
Characteristic
Operation accuracy
Start time
Reset time
Operate time accuracy
Step
Default
0.005
-0.010
10
200
10
200
0.001
0.998
10
300
Step
Default
1=on
Step
Default
1
50
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
f<
±5 mHz
df/dt
±100 mHz/s (in range |df/dt| < 5 Hz/s)
± 2.0% of the set value (in range 5 Hz/s < |df/dt| <
15 Hz/s)
f<
<80 ms
df/dt
<120 ms
<150 ms
±1.0% of the set value or ±30 ms
1MRS758755 A
Description
Setting of frequency gradient for df/dt
detection
Time delay to operate for under frequency
stage
Time delay to operate for df/dt stage
Restore frequency setting value
Time delay to restore
Description
Operation Off / On
Description
Time delay after which the definite timers
will reset
Unit
Description
%
Start duration
Status
REC615 and RER615
Technical Manual