Section 4
Protection functions
250
Table 264:
DPHHPDOC Monitored data
Name
Type
START_DUR
FLOAT32
FAULT_DIR
Enum
DIRECTION
Enum
DIR_A
Enum
DIR_B
Enum
DIR_C
Enum
ANGLE_A
FLOAT32
ANGLE_B
FLOAT32
ANGLE_C
FLOAT32
VMEM_USED
BOOLEAN
DPHHPDOC
Enum
Values (Range)
Unit
0.00...100.00
%
0=unknown
1=forward
2=backward
3=both
0=unknown
1=forward
2=backward
3=both
0=unknown
1=forward
2=backward
-1=both
0=unknown
1=forward
2=backward
-1=both
0=unknown
1=forward
2=backward
-1=both
-180.00...180.00
deg
-180.00...180.00
deg
-180.00...180.00
deg
0=False
1=True
1=on
2=blocked
3=test
4=test/blocked
5=off
1MRS758755 A
Description
Ratio of start time /
operate time
Detected fault direction
Direction information
Direction phase A
Direction phase B
Direction phase C
Calculated angle
difference, Phase A
Calculated angle
difference, Phase B
Calculated angle
difference, Phase C
Voltage memory in use
status
Status
REC615 and RER615