1MRS758755 A
Table 502:
CCBRBRF Non group settings (Advanced)
Parameter
Values (Range)
CB fault delay
Measurement mode
Trip pulse time
Start latching mode
5.2.8
5.2.9
5.2.10
REC615 and RER615
Technical Manual
Unit
0...60000
ms
2=DFT
3=Peak-to-Peak
0...60000
ms
1=Rising edge
2=Level sensitive

Monitored data

Table 503:
CCBRBRF Monitored data
Name
CCBRBRF
Technical data
Table 504:
CCBRBRF Technical data
Characteristic
Operation accuracy
Operate time accuracy
Reset time
Retardation time
Technical revision history
Table 505:
CCBRBRF Technical revision history
Technical revision
B
C
D
E
Step
Default
10
5000
3=Peak-to-Peak
10
200
1=Rising edge
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the measured
current: f
±1.5% of the set value or ±0.002 × I
±1.0% of the set value or ±20 ms
Typically 40 ms
<20 ms
Change
Default trip pulse time changed to 150 ms
Added new setting parameter
Maximum value changed to 2.00 xIn for the
Current value setting.
Internal improvement.
Maximum value for
value Res changed from "1.00 x In" to "2.00 x In".
Protection related functions
Description
Circuit breaker faulty delay
Phase current measurement mode of
function
Pulse length of retrip and backup trip
outputs
Start reset delayed or immediately
Unit
Description
Status
±2 Hz
n
Start latching mode .
Current value and Current
Section 5
n
475