Settings - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.1.4.7
Table 279:
PHPTUC Group settings (Basic)
Parameter
Current block value
Start value
Operate delay time
Table 280:
PHPTUC Non group settings (Basic)
Parameter
Operation
Operation mode
Table 281:
PHPTUC Non group settings (Advanced)
Parameter
Reset delay time
4.1.4.8
4.1.4.9
262

Settings

Values (Range)
Unit
0.00...0.50
xIn
0.01...1.00
xIn
50...200000
ms
Values (Range)
Unit
1=on
5=off
1=Three Phase
2=Single Phase
Values (Range)
Unit
0...60000
ms
Monitored data
Table 282:
PHPTUC Monitored data
Name
START_DUR
PHPTUC
Technical data
Table 283:
PHPTUC Technical data
Characteristic
Operation accuracy
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Step
Default
0.01
0.10
0.01
0.50
10
2000
Step
Default
1=on
1=Three Phase
Step
Default
1
20
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the current
measured: f
±1.5% of the set value or ±0.002 × I
Typically <55 ms
<40 ms
Typically 1.04
<35 ms
mode ±1.0% of the set value or ±20 ms
1MRS758755 A
Description
Low current setting to block internally
Current setting to start
Operate delay time
Description
Operation Off / On
Number of phases needed to start
Description
Reset delay time
Unit
Description
%
Ratio of start time /
operate time
Status
±2 Hz
n
n
REC615 and RER615
Technical Manual