Settings - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
6.2.7
Table 539:
SEQSPVC Non group settings (Basic)
Parameter
Values (Range)
Operation
Table 540:
SEQSPVC Non group settings (Advanced)
Parameter
Values (Range)
Neg Seq current Lev
Neg Seq voltage Lev
Current change rate
Voltage change rate
Change rate enable
Min Op voltage delta
Min Op current delta
Seal in voltage
Enable seal in
Current dead Lin Val
REC615 and RER615
Technical Manual
Name
CB_CLOSED
DISCON_OPEN
MINCB_OPEN
Table 538:
SEQSPVC Output signals
Name
FUSEF_3PH
FUSEF_U

Settings

Unit
1=on
5=off
Unit
0.03...0.20
xIn
0.03...0.20
xUn
0.01...0.50
xIn
0.25...0.90
xUn
0=False
1=True
0.01...1.00
xUn
0.01...1.00
xIn
0.01...1.00
xUn
0=False
1=True
0.05...1.00
xIn
Type
Default
Description
BOOLEAN
0=False
Active when circuit breaker is closed
BOOLEAN
0=False
Active when line disconnector is open
BOOLEAN
0=False
Active when external MCB opens protected voltage
circuit
Type
Description
BOOLEAN
Three-phase start of function
BOOLEAN
General start of function
Step
Default
1=on
Step
Default
0.01
0.03
0.01
0.10
0.01
0.15
0.01
0.40
0=False
0.01
0.50
0.01
0.10
0.01
0.50
0=False
0.01
0.05
Section 6
Supervision functions
Description
Operation Off / On
Description
Operate level of neg seq undercurrent
element
Operate level of neg seq overvoltage
element
Operate level of change in phase current
Operate level of change in phase voltage
Enabling operation of change based
function
Minimum operate level of phase voltage
for delta calculation
Minimum operate level of phase current
for delta calculation
Operate level of seal-in phase voltage
Enabling seal in functionality
Operate level for open phase current
detection
525