1MRS758755 A
9.5.6
REC615 and RER615
Technical Manual
Load fault detections on busbar, such as overcurrent and earth-fault functions are
connected as grouped protection input to BLOCK. Auto mode OFF/ON is connected to
input BLOCK.
GUID-B9F3739B-FBA6-4F2D-AD69-02B026229C77 V1 EN
Figure 355:
Signal scheme illustrating an automatic transfer switch and an
automatic reconnection operation caused by a temporary under-
voltage on the preferred bus 1 (all other excluded inputs are "FALSE"
during the sequence)

Signals

Table 676:
ATSABTC Input signals
Name
Type
BLOCK
BOOLEAN
UN_U_BUS1
BOOLEAN
UN_U_BUS2
BOOLEAN
CB1_POSOPEN
BOOLEAN
CB1_POSCLOSE
BOOLEAN
CB2_POSOPEN
BOOLEAN
CB2_POSCLOSE
BOOLEAN
Default
Description
0=False
Blocking of function
0=False
Under-voltage on bus 1
0=False
Under-voltage on bus 2
0=False
Circuit breaker open status for bus 1
0=False
Circuit breaker close status for bus 1
0=False
Circuit breaker open status for bus 2
0=False
Circuit breaker close status for bus 2
Section 9
Control functions
671