ABB RELION Series Technical Manual page 788

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 14
Technical data
782
Table 733:
Energizing inputs
Description
Rated frequency
Current inputs
Rated current, I
Thermal withstand capability
Continuously
For 1 s
Dynamic current withstand
Half-wave value
Input impedance
Voltage inputs
Rated voltage
Voltage withstand
Continuous
For 10 s
Burden at rated voltage
1) Ordering option for residual current input
2) Residual current and/or phase current
Table 734:
Energizing inputs of SIM0001
Description
Voltage sensor input
Rated voltage
Continuous voltage
withstand
Input impedance at 50/60
Hz
Voltage inputs
Rated voltage
Voltage withstand
Burden at rated voltage
1) This range is covered with a sensor division ratio of 10 000:1 if the input type is set as CVD sensor.
2) Test to this voltage
3) Neutral input impedance is close to zero
Value
50/60 Hz
0.2/1 A
n
1)
4 A
1)
100 A
1)
250 A
<100 mΩ
60...210 V AC
240 V AC
360 V AC
<0.05 VA
Value
5 kV...38 kV
125 V AC
3)
1 MΩ
60...210 V AC
Continuous
240 V AC
For 10 s
360 V AC
<0.05 VA
1MRS758755 A
1)
2)
1/5 A
20 A
500 A
1250 A
<20 mΩ
1)
1)
2)
REC615 and RER615
Technical Manual