Variation Validation - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
10.3.4.3
REC615 and RER615
Technical Manual
Voltage swell set
U_A
U_C
Voltage dip set
Voltage Int set
SWELLST
DIPST
INTST
SWELLST
DIPST
INTST
GUID-F44C8E6E-9354-44E4-9B2E-600D66B76C1A V1 EN
Figure 362:
Detection of three-phase voltage interruption
The module measures voltage variation magnitude on each phase separately, that is,
there are phase-segregated outputs ST_A, ST_B and ST_C for voltage variation
indication. The configuration parameter Phase supervision defines which voltage
phase or phases are monitored. If a voltage phase is selected to be monitored, the
function assumes it to be connected to a voltage measurement channel. In other words,
if an unconnected phase is monitored, the function falsely detects a voltage
interruption in that phase.
The maximum magnitude and depth are defined as percentage values calculated from
the difference between the reference and the measured voltage. For example, a dip to
70 percent means that the minimum voltage dip magnitude variation is 70 percent of
the reference voltage amplitude.
The activation of the BLOCK input resets the function and outputs.

Variation validation

The validation criterion for voltage variation is that the measured total variation
duration is between the set minimum and maximum durations (Either one of VVa dip
time 1, VVa swell time 1 or VVa Int time 1, depending on the variation type, and VVa
Dur Max). The maximum variation duration setting is the same for all variation types.
Power quality measurement functions
A) Three phase mode
B) Single phase mode
Section 10
U_B
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
683