ABB RELION Series Technical Manual page 339

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
REC615 and RER615
Technical Manual
E
A
E
B
E
C
R
n
Uo
L
cc
R
cc
Forward fault,
unearthed network:
Yo ≈ j*(I
-I
)/U
eTot
eFd
Reverse fault:
Yo ≈ -j*I
GUID-5DB19698-38F9-433E-954F-4EBDBA5B63BD V1 EN
Figure 168:
Admittance calculation during a forward fault
When the network is fully compensated in compensated networks,
theoretically during a forward fault, the imaginary part of the
measured admittance equals the susceptance of the protected feeder
with a negative sign. The discrimination between a forward and
reverse fault must therefore be based on the real part of the measured
admittance, that is, conductance. Thus, the best selectivity is achieved
Io
A B C
~
~
~
high resistance earthed network:
Im(Yo)
ph
/U
eFd
ph
Forward fault, compensated network:
Yo ≈ (I
+ j*(I
*(1-K) - I
rcc
eTot
Section 4
Protection functions
Protected feeder
Y
Fd
I
eFd
Background network
Y
Bg
Forward fault,
Yo ≈ (I
+j*(I
-I
))/U
Rn
eTot
eFd
ph
Under-comp. (K<1)
Re(Yo)
Resonance (K=1)
Over-comp. (K>1)
))/U
eFd
ph
Forward
Fault
I
eTot
(I
- I
)
eTot
eFd
333