Technical Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
10.4.9
REC615 and RER615
Technical Manual
Name
Type
Max unbalance Volt
FLOAT32
Time Max Unb Volt
Timestamp
Alarm high mean Dur
FLOAT32
Max unbalance Volt
FLOAT32
Time Max Unb Volt
Timestamp
VSQVUB
Enum

Technical data

Table 706:
VSQVUB Technical data
Characteristic
Operation accuracy
Reset ratio
Power quality measurement functions
Values (Range)
Unit
0.00...150.00
%
0.000...3600.000
s
0.00...150.00
%
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
±1.5% of the set value or ±0.002 × U
Typically 0.96
Section 10
Description
Maximum 3 seconds
unbalance voltage
Time stamp of maximum
voltage unbalance
Time duration for alarm
high mean unbalance
Maximum 3 seconds
unbalance voltage
Time stamp of maximum
voltage unbalance
Status
n
707

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615