Section 9
Control functions
9.4.7
660
parameter to "1" and connecting the protection start information to the corresponding
DEL_INIT_ input.
When the function detects a closing of the circuit breaker, that is, any other closing
except the reclosing done by the function itself, it always prohibits shot initiation for
the time set with the Reclaim time parameter. Furthermore, if the Fourth delay in
SOTF parameter is "1", the Str _ delay shot 4 parameter delays are also activated.
Example 1
The protection operation time is 0.5 seconds, the Fourth delay in SOTF parameter is
set to "1" and the Str 2 delay shot 4 parameter is 0.05 seconds. The protection start
signal is connected to the DEL_INIT_2 input.
If the protection starts after the circuit breaker closes, the fast trip follows after the set
0.05 seconds. The total trip time is the protection start delay + 0.05 seconds + the time
it takes to open the circuit breaker.

Signals

Table 667:
DARREC Input signals
Name
Type
INIT_1
BOOLEAN
INIT_2
BOOLEAN
INIT_3
BOOLEAN
INIT_4
BOOLEAN
INIT_5
BOOLEAN
INIT_6
BOOLEAN
DEL_INIT_2
BOOLEAN
DEL_INIT_3
BOOLEAN
DEL_INIT_4
BOOLEAN
BLK_RECL_T
BOOLEAN
BLK_RCLM_T
BOOLEAN
BLK_THERM
BOOLEAN
CB_POS
BOOLEAN
CB_READY
BOOLEAN
INC_SHOTP
BOOLEAN
INHIBIT_RECL
BOOLEAN
RECL_ON
BOOLEAN
SYNC
BOOLEAN
Default
Description
0=False
AR initialization / blocking signal 1
0=False
AR initialization / blocking signal 2
0=False
AR initialization / blocking signal 3
0=False
AR initialization / blocking signal 4
0=False
AR initialization / blocking signal 5
0=False
AR initialization / blocking signal 6
0=False
Delayed AR initialization / blocking signal 2
0=False
Delayed AR initialization / blocking signal 3
0=False
Delayed AR initialization / blocking signal 4
0=False
Blocks and resets reclose time
0=False
Blocks and resets reclaim time
0=False
Blocks and holds the reclose shot from the thermal
overload
0=False
Circuit breaker position input
1=True
Circuit breaker status signal
0=False
A zone sequence coordination signal
0=False
Interrupts and inhibits reclosing sequence
0=False
Level sensitive signal for allowing (high) / not
allowing (low) reclosing
0=False
Synchronizing check fulfilled
1MRS758755 A
REC615 and RER615
Technical Manual