1MRS758755 A
REC615 and RER615
Technical Manual
Parameter
Values (Range) Unit
High trigger
0.00...60.00
level
Low trigger
0.00...2.00
level
Storage mode
0=Waveform
1=Trend /
cycle
1) Recordable values are available only in trend mode. In waveform mode, samples for this signal type are
constant zeroes. However, these signal types can be used to trigger the recorder on limit violations of
the corresponding analog channel.
Table 624:
RDRE Non-group binary channel settings
Parameter
Values (Range) Unit
Operation
1=on
5=off
Level trigger
1=Positive or
mode
Rising
2=Negative or
Falling
3=Both
4=Level
trigger off
Storage mode
0=Waveform
1=Trend /
cycle
Channel id
0 to 64
text
characters,
alphanumeric
Table 625:
RDRE Control data
Parameter
Values (Range) Unit
Trig recording
0=Cancel
1=Trig
Clear
0=Cancel
recordings
1=Clear
Measurement functions
Step
pu
0.01
pu
0.01
1
Step
1
1
1
Step
Section 8
Default
Description
10.00
High trigger
level for the
analog
channel
0.00
Low trigger
level for the
analog
channel
0
Storage mode
for the analog
channel
Default
Description
5=off
Binary
channel is
enabled or
disabled
1=Rising
Level trigger
mode for the
binary
channel
0
Storage mode
for the binary
channel
DR binary
Identification
channel X
text for the
analog
channel used
in the
COMTRADE
format
Default
Description
Trigger the
disturbance
recording
Clear all
recordings
currently in
memory
601