The circuit-breaker condition monitoring function SSCBR is used to monitor different
parameters of the circuit breaker. The breaker requires maintenance when the number
of operations has reached a predefined value. The energy is calculated from the
measured input currents as a sum of I
calculated values exceed the threshold settings.
The function contains a blocking functionality. It is possible to block the function
outputs, if desired.
Operation principle
The circuit breaker condition monitoring function includes different metering and
monitoring sub-functions. The functions can be enabled and disabled with the
Operation setting. The corresponding parameter values are "On" and "Off". The
operation counters are cleared when Operation is set to "Off".
The operation of SSCBR can be described with a module diagram. All the modules in
the diagram are explained in the next sections.
Condition monitoring functions
IEC 61850
IEC 60617
identification
identification
SSCBR
CBCM
y
t values. Alarms are generated when the
Section 7
ANSI/IEEE C37.2
device number
CBCM
535

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents