ABB RELION Series Technical Manual page 499

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
REC615 and RER615
Technical Manual
either given in ohm/km and section length in km, or ohm/mile and section length in
miles. The resulting Flt distance matches the units entered for the line section lengths.
Positive-sequence impedance values
Fault location requires accurate setting values for line impedances. Positive-sequence
impedances are required both for location of short circuits and earth faults. As data
sheet impedance per unit values are generally valid only for a certain tower
configuration, the values should be adjusted according to the actual installation
configuration. This minimizes the fault location errors caused by inaccurate settings.
The positive-sequence reactance per unit and per phase can be calculated with a
following approximation equation which applies to symmetrically transposed three-
phase aluminium overhead lines without ground wires.
a
4
en
10
2
ln
0 5
X
ω
+
1
n
r
GUID-B7F3697A-7C8E-4BF6-A63C-7BFD307DD128 V2 EN
ω
2 × π × f
n
a
en
a
3
(
12
GUID-DA850ABF-239A-4AB5-B63B-F0B54557CF2E V2 EN
the geometric average of phase distances [m]
a
distance [m] between phases x and y
xy
r
radius [m] for single conductor
GUID-40949A85-D97F-4639-9D61-3CAE997D28D3 V2 EN
Figure 255:
Typical distribution line tower configurations
Example values of positive-sequence impedances for typical medium voltage
overhead-lines are given in the following tables.
Table 515:
Positive-sequence impedance values for typical 11 kV conductors, "Flat" tower
configuration assumed
Name
ACSR 50 SQ.mm
ACSR 500 SQ.mm
Protection related functions
. [ /
]
km
, where f
= fundamental frequency [Hz]
n
n
a
a
)
23
31
R1 [Ω/km]
0.532
0.0725
Section 5
(Equation 59)
X1 [Ω/km]
0.373
0.270
493

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents