Signals - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 4
Protection functions
4.2.5.6
4.2.5.7
Table 371:
HAEFPTOC Group settings (Basic)
Parameter
Start value
Time multiplier
Operate delay time
Operating curve type
Table 372:
HAEFPTOC Group settings (Advanced)
Parameter
Minimum operate time
Type of reset curve
Enable reference use
358

Signals

Table 369:
HAEFPTOC Input signals
Name
Io
BLOCK
I_REF_RES
Table 370:
HAEFPTOC Output signals
Name
OPERATE
START
Settings
Values (Range)
Unit
0.05...5.00
xIn
0.05...15.00
100...200000
ms
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Values (Range)
Unit
100...200000
ms
1=Immediate
2=Def time reset
3=Inverse reset
0=False
1=True
Type
Default
Description
SIGNAL
0
Residual current
BOOLEAN
0=False
Block signal for activating the blocking mode
FLOAT32
0.0
Reference current
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.01
0.10
0.01
1.00
10
600
15=IEC Def. Time
Step
Default
10
500
1=Immediate
0=False
1MRS758755 A
Description
Start value
Time multiplier in IEC/ANSI IDMT curves
Operate delay time
Selection of time delay curve type
Description
Minimum operate time for IDMT curves
Selection of reset curve type
Enable using current reference from other
IEDs instead of stand-alone
REC615 and RER615
Technical Manual