Section 3
Basic functions
3.12.3
98
Sensor
Transducer
GUID-FBB50B49-0EFE-4D1C-AB71-204C3E170C1D V2 EN
Figure 44:
mA wiring connection for RTD/mA card

Signals

Table 40:
Output signals
Name
Type
ALARM
BOOLEAN
WARNING
BOOLEAN
AI_VAL1
FLOAT32
AI_VAL2
FLOAT32
AI_VAL3
FLOAT32
AI_VAL4
FLOAT32
AI_VAL5
FLOAT32
AI_VAL6
FLOAT32
AI_VAL7
FLOAT32
AI_VAL8
FLOAT32
Description
General alarm
General warning
mA input, Connectors 1-2, instantaneous value
mA input, Connectors 3-4, instantaneous value
RTD input, Connectors 5-6-11c, instantaneous
value
RTD input, Connectors 7-8-11c, instantaneous
value
RTD input, Connectors 9-10-11c, instantaneous
value
RTD input, Connectors 13-14-12c, instantaneous
value
RTD input, Connectors 15-16-12c, instantaneous
value
RTD input, Connectors 17-18-12c, instantaneous
value
1MRS758755 A
X130
+
1
Shunt
(44 Ω)
-
2
...
...
...
8
REC615 and RER615
Technical Manual