1MRS758755 A
3.14.1
3.14.1.1
3.14.1.2
3.14.1.3
3.14.2
3.14.2.1
REC615 and RER615
Technical Manual
Common signals
The VALID output indicates the validity of received GOOSE data, which means in
case of valid, that the GOOSE communication is working and received data quality
bits (if configured) indicate good process data. Invalid status is caused either by bad
data quality bits or GOOSE communication failure. See IEC 61850 engineering guide
for details.
The OUT output passes the received GOOSE value for the application. Default value
(0) is used if VALID output indicates invalid status. The IN input is defined in the
GOOSE configuration and can always be seen in SMT sheet.
Settings

GOOSERCV_BIN function block

Function block

GUID-44EF4D6E-7389-455C-BDE5-B127678E2CBC V1 EN
Figure 48:

Function block

Functionality

The GOOSERCV_BIN function is used to connect the GOOSE binary inputs to the
application.

Signals

Table 52:
GOOSERCV_BIN Output signals
Name
Type
OUT
BOOLEAN
VALID
BOOLEAN

GOOSERCV_DP function block

Function block
GUID-63C0C3EE-1C0E-4F78-A06E-3E84F457FC98 V1 EN
Figure 49:
Function block
Basic functions
Description
Output signal
Output signal
Section 3