1MRS758755 A
Table 297:
FEFLPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
Curve parameter A
Curve parameter B
Curve parameter C
Curve parameter D
Curve parameter E
Table 298:
FEFLPTOC Non group settings (Advanced)
Parameter
Values (Range)
Minimum operate time
Reset delay time
Measurement mode
Io signal Sel
Table 299:
EFLPTOC Group settings (Basic)
Parameter
Values (Range)
Start value
Start value Mult
Time multiplier
Operate delay time
Operating curve type
REC615 and RER615
Technical Manual
Unit
1=on
5=off
0.0086...120.0000
0.0000...0.7120
0.02...2.00
0.46...30.00
0.0...1.0
Unit
20...60000
ms
0...60000
ms
1=RMS
2=DFT
3=Peak-to-Peak
1=Measured Io
2=Calculated Io
Unit
0.010...5.000
xIn
0.8...10.0
0.05...15.00
40...200000
ms
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Step
Default
1=on
1
28.2000
1
0.1217
1
2.00
1
29.10
1
1.0
Step
Default
1
20
1
20
2=DFT
1=Measured Io
Step
Default
0.005
0.010
0.1
1.0
0.01
1.00
10
40
15=IEC Def. Time
Section 4
Protection functions
Description
Operation Off / On
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer programmable
curve
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve
Description
Minimum operate time for IDMT curves
Reset delay time
Selects used measurement mode
Selection for used Io signal
Description
Start value
Multiplier for scaling the start value
Time multiplier in IEC/ANSI IDMT curves
Operate delay time
Selection of time delay curve type
273