1MRS758755 A
REC615 and RER615
Technical Manual
Equation 13
shows that in case of outside faults, the measured admittance equals the
admittance of the protected feeder with a negative sign. The measured admittance is
dominantly reactive; the small resistive part of the measured admittance is due to the
leakage losses of the feeder. Theoretically, the measured admittance is located in the
third quadrant in the admittance plane close to the im(Yo) axis, see
The result of
method. In compensated networks the compensation degree does not
affect the result. This enables a straightforward setting principle for
the neutral admittance protection: admittance characteristic is set to
cover the value Yo = –Y
Due to inaccuracies in voltage and current measurement, the small
real part of the calculated neutral admittance may appear as positive,
which brings the measured admittance in the fourth quadrant in the
admittance plane. This should be considered when setting the
admittance characteristic.
Equation 13
is valid regardless of the neutral earthing
with a suitable margin.
Fdtot
Section 4
Protection functions
Figure
167.
329