Settings - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
4.4.4.7
Table 442:
NSPTOV Group settings (Basic)
Parameter
Values (Range)
Start value
Operate delay time
Table 443:
NSPTOV Non group settings (Basic)
Parameter
Values (Range)
Operation
Table 444:
NSPTOV Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
4.4.4.8
REC615 and RER615
Technical Manual
Table 441:
NSPTOV Output signals
Name
OPERATE
START

Settings

Unit
0.010...1.000
xUn
40...120000
ms
Unit
1=on
5=off
Unit
0...60000
ms
Monitored data
Table 445:
NSPTOV Monitored data
Name
START_DUR
NSPTOV
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.001
0.030
1
40
Step
Default
1=on
Step
Default
1
20
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Section 4
Protection functions
Description
Start value
Operate delay time
Description
Operation Off / On
Description
Reset delay time
Unit
Description
%
Ratio of start time /
operate time
Status
429

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents