Section 3
Basic functions
Parameter
DST off date (month)
DST off day (weekday)
DST offset
3.5
3.5.1
3.5.2
60
Values (Range)
Unit
1=January
2=February
3=March
4=April
5=May
6=June
7=July
8=August
9=September
10=October
11=November
12=December
0=reserved
1=Monday
2=Tuesday
3=Wednesday
4=Thursday
5=Friday
6=Saturday
7=Sunday
-720...720
min

Parameter setting groups

Function block

GUID-DFF8F71A-895C-4C06-B287-63C3CA26154C V2 EN
Figure 22:
Function block

Functionality

The protection relay supports six setting groups. Each setting group contains
parameters categorized as group settings inside application functions. The customer
can change the active setting group at run time.
The active setting group can be changed by a parameter or via binary inputs depending
on the mode selected with the Configuration/Setting Group/SG operation mode
setting.
The default value of all inputs is FALSE, which makes it possible to use only the
required number of inputs and leave the rest disconnected. The setting group selection
is not dependent on the SG_x_ACT outputs.
Step
Default
9=September
0=reserved
1
60
1MRS758755 A
Description
Daylight saving time off, date (dd:mm)
Daylight saving time off, day of week
Daylight saving time offset
REC615 and RER615