1MRS758755 A
3.19.1.4
3.19.1.5
3.19.2
3.19.2.1
3.19.2.2
REC615 and RER615
Technical Manual

Settings

Table 198:
Redundancy settings
Parameter
Values (Range) Unit
Redundant
None
mode
PRP
HSR

Monitored data

Monitored data is available in four locations.
Monitoring/Communication/Ethernet/Activity/CHLIV_A
Monitoring/Communication/Ethernet/Activity/REDCHLIV_B
Monitoring/Communication/Ethernet/Link statuses/LNKLIV_A
Monitoring/Communication/Ethernet/Link statuses/REDLNKLIV_B

Ethernet channel supervision SCHLCCH

Function block

GUID-DBA25BB9-6BF5-4C45-A39F-1920113A22F2 V1 EN
Figure 112:
Function block

Functionality

Ethernet channel supervision SCHLCCH represents X1/LAN, X2/LAN and X3/LAN
Ethernet channels.
An unused Ethernet port can be set "Off" with the setting Configuration/
Communication/Ethernet/Rear port(s)/Port x Mode. This setting closes the port
from software, disabling the Ethernet communication in that port. Closing an unused
Ethernet port enhances the cyber security of the relay.
Step
Default Description
None
Mode selection for Ethernet switch on
redundant communication modules.
The "None" mode is used with normal
and Self-healing Ethernet topologies.