1MRS758755 A
3.12.2.10
REC615 and RER615
Technical Manual
Temp
Platinum TCR 0.00385
°C
Pt 100
80
130.89
90
134.7
100
138.5
120
146.06
140
153.58
150
-
160
161.04
180
168.46
200
175.84
RTD/mA input connection
RTD inputs can be used with a 2-wire or 3-wire connection with common ground.
When using the 3-wire connection, it is important that all three wires connecting the
sensor are symmetrical, that is, the wires are of the same type and length. Thus the wire
resistance is automatically compensated.
GUID-BC4182F7-F701-4E09-AB3D-EFB48280F097 V1 EN
Figure 36:
Three RTD/resistance sensors connected according to the 3-wire
connection
Nickel TCR 0.00618
Pt 250
Ni 100
327.225
148.3
336.75
154.9
346.25
161.8
365.15
176
383.95
190.9
-
198.6
402.6
206.6
421.15
223.2
439.6
240.7
Section 3
Basic functions
Ni 120
Ni 250
177.96
370.75
185.88
387.25
194.16
404.5
211.2
440
229.08
477.25
238.32
496.5
247.92
516.5
267.84
558
288.84
601.75
Copper TCR
0.00427
Cu 10
12.124
-
12.897
13.669
14.442
-
15.217
-
-
93