1MRS758755 A
Parameter
Values (Range)
Operate delay time
Operating curve type
Type of reset curve
REC615 and RER615
Technical Manual
Unit
40...200000
ms
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
-1=Recloser 1
-2=Recloser 2
-3=Recloser 3
-4=Recloser 4
-5=Recloser 5
-6=Recloser 6
-7=Recloser 7
-8=Recloser 8
-9=Recloser 8+
-10=Recloser 8*
-11=Recloser 9
-12=Recloser 11
-13=Recloser 13
-14=Recloser 14
-15=Recloser 15
-16=Recloser 16
-17=Recloser 17
-18=Recloser 18
-19=Recloser A
-20=Recloser B
-21=Recloser C
-22=Recloser D
-23=Recloser E
-24=Recloser F
-25=Recloser G
-26=Recloser H
-27=Recloser J
-28=Recloser Kg
-29=Recloser Kp
-30=Recloser L
-31=Recloser M
-32=Recloser N
-33=Recloser P
-34=Recloser R
-35=Recloser T
-36=Recloser V
-37=Recloser W
-38=Recloser Y
-39=Recloser Z
1=Immediate
2=Def time reset
3=Inverse reset
Step
Default
10
40
15=IEC Def. Time
1=Immediate
Section 4
Protection functions
Description
Operate delay time
Selection of time delay curve type
Selection of reset curve type