ABB RELION Series Technical Manual page 388

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 4
Protection functions
382
1
1
1
I
(
G
j B
=
+ ⋅
o stab
ostab
ostab
GUID-5E6BA356-F1BE-42D6-A6A1-308F93255F7E V1 EN
The stabilized fundamental frequency residual current estimate, which is obtained (after
1
I
conversion) from the corresponding admittance value by multiplying it with the system
o stab
nominal phase-to-earth voltage value.
The real-part of stabilized fundamental frequency residual current estimate.
1
I
o Cosstab
The imaginary-part of stabilized fundamental frequency residual current estimate.
1
I
o Sinstab
The main advantage of the filtering method is that due to the admittance calculation,
the resulting current value does not depend on the value of fault resistance, that is, the
estimated current magnitude equals the value that would be measured during a solid
earth fault (R
= 0 Ω). Another advantage of the method is that it is capable of
f
estimating correct current magnitude also during intermittent or restriking faults.
The setting Min operate current defines the minimum operate current.
Setting Operating quantity defines whether the current magnitude supervision is
based on either the "Adaptive" or "Amplitude" methods.
When "Adaptive" is selected, the method adapts the principle of magnitude
supervision automatically to the system earthing condition. In case the phase angle of
accumulated sum admittance phasor is greater than 45 degrees, the set minimum
operate current threshold is compared to the amplitude of
case the phase angle of accumulated sum admittance phasor is below 45 degrees, the
set minimum operate current threshold is compared to the resistive component of
1
I
. This automatic adaptation of the magnitude supervision enables secure and
o stab
dependable directional determination in compensated networks, and it is also valid
when the network is unearthed (compensation coil is switched off).
In case operation direction is set to reverse, the resistive and amplitude sectors are
mirrored in the operation characteristics.
When "Amplitude" is selected, the set minimum operate current threshold is
compared to the amplitude of
In compensated networks, setting Operating quantity should be set to
"Adaptive". This enables secure and dependable directional
determination on compensated networks and it is also valid when
compensation coil is switched off and network becomes unearthed.
1
)
U
I
j I
=
+ ⋅
baseres
oCosstab
1
I
. This selection can be used in unearthed networks.
o stab
1MRS758755 A
1
oSinsta
b b
(Equation 41)
1
I
(see
Figure
o stab
REC615 and RER615
Technical Manual
199). In

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents