ABB RELION Series Technical Manual page 251

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
Table 253:
FDPHLPDOC Non group settings (Advanced)
Parameter
Values (Range)
Minimum operate time
Reset delay time
Measurement mode
Min operate current
Min operate voltage
Table 254:
DPHLPDOC Group settings (Basic)
Parameter
Values (Range)
Start value
Start value Mult
Time multiplier
Operate delay time
Operating curve type
Directional mode
Characteristic angle
Max forward angle
Max reverse angle
Min forward angle
Min reverse angle
REC615 and RER615
Technical Manual
Unit
40...60000
ms
0...60000
ms
1=RMS
2=DFT
3=Peak-to-Peak
0.01...1.00
xIn
0.01...1.00
xUn
Unit
0.05...5.00
xIn
0.8...10.0
0.05...15.00
40...200000
ms
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
1=Non-directional
2=Forward
3=Reverse
-179...180
deg
0...90
deg
0...90
deg
0...90
deg
0...90
deg
Step
Default
1
40
1
20
2=DFT
0.01
0.01
0.01
0.01
Step
Default
0.01
0.05
0.1
1.0
0.01
1.00
10
40
15=IEC Def. Time
2=Forward
1
60
1
80
1
80
1
80
1
80
Section 4
Protection functions
Description
Minimum operate time for IDMT curves
Reset delay time
Selects used measurement mode
Minimum operating current
Minimum operating voltage
Description
Start value
Multiplier for scaling the start value
Time multiplier in IEC/ANSI IDMT curves
Operate delay time
Selection of time delay curve type
Directional mode
Characteristic angle
Maximum phase angle in forward
direction
Maximum phase angle in reverse
direction
Minimum phase angle in forward direction
Minimum phase angle in reverse direction
245