Signals - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 7
Condition monitoring functions
7.1.6
548
log
Directional Coef
=
I
log
I
A070794 V2 EN
I
Rated operating current = 630 A
r
I
Rated fault current = 16 kA
f
A
Op number rated = 30000
B
Op number fault = 20
Calculation for estimating the remaining life
Figure 291
shows that there are 30,000 possible operations at the rated operating
current of 630 A and 20 operations at the rated fault current 16 kA. Therefore, if the
tripping current is 10 kA, one operation at 10 kA is equivalent to 30,000/60=500
operations at the rated current. It is also assumed that prior to this tripping, the
remaining life of the circuit breaker is 15,000 operations. Therefore, after one
operation of 10 kA, the remaining life of the circuit breaker is 15,000-500=14,500 at
the rated operating current.
Remaining life reduction =
GUID-5AA23DAD-AAF0-4D03-844F-216C80F80789 V1 EN
Spring-charged indication
For normal operation of the circuit breaker, the circuit breaker spring should be
charged within a specified time. Therefore, detecting long spring-charging time
indicates that it is time for the circuit breaker maintenance. The last value of the
spring-charging time can be used as a service value.
Gas pressure supervision
The gas pressure supervision monitors the gas pressure inside the arc chamber. When
the pressure becomes too low compared to the required value, the circuit breaker
operations are locked. A binary input is available based on the pressure levels in the
function, and alarms are generated based on these inputs.

Signals

Table 556:
SSCBR Input signals
Name
Type
I_A
SIGNAL
I_B
SIGNAL
I_C
SIGNAL
Table continues on next page
B
A
. 2 2609
= −
f
r
Directional Coef
I
I
r
Default
Description
0
Phase A current
0
Phase B current
0
Phase C current
1MRS758755 A
(Equation 66)
(Equation 67)
REC615 and RER615
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents