Monitored Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 3
Basic functions
Parameter
Value maximum
Value minimum
Val high high limit
Value high limit
Value low limit
Value low low limit
Value deadband
3.12.5
100
Values (Range)
Unit
-10000.0...10000.0
-10000.0...10000.0
-10000.0...10000.0
-10000.0...10000.0
-10000.0...10000.0
-10000.0...10000.0
100...100000

Monitored data

Table 43:
Monitored data
Name
AI_DB1
AI_RANGE1
AI_DB2
AI_RANGE2
AI_DB3
AI_RANGE3
AI_DB4
AI_RANGE4
AI_DB5
Table continues on next page
Step
Default
1
10000.0
1
-10000.0
1
10000.0
1
10000.0
1
-10000.0
1
-10000.0
1
1000
Type
Values (Range)
FLOAT32
-10000.0...10000
.0
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
FLOAT32
-10000.0...10000
.0
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
FLOAT32
-10000.0...10000
.0
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
FLOAT32
-10000.0...10000
.0
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
FLOAT32
-10000.0...10000
.0
1MRS758755 A
Description
Maximum output value for scaling and
supervision
Minimum output value for scaling and
supervision
Output value high alarm limit for
supervision
Output value high warning limit for
supervision
Output value low warning limit for
supervision
Output value low alarm limit for
supervision
Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
Unit
Description
mA input, Connectors
1-2, reported value
mA input, Connectors
1-2, range
mA input, Connectors
3-4, reported value
mA input, Connectors
3-4, range
RTD input, Connectors
5-6-11c, reported value
RTD input, Connectors
5-6-11c, range
RTD input, Connectors
7-8-11c, reported value
RTD input, Connectors
7-8-11c, range
RTD input, Connectors
9-10-11c, reported value
REC615 and RER615
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents