Signals - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 5
Protection related functions
5.2.6
5.2.7
Table 501:
CCBRBRF Non group settings (Basic)
Parameter
Operation
Current value
Current value Res
CB failure trip mode
CB failure mode
CB fail retrip mode
Retrip time
CB failure delay
474

Signals

Table 499:
CCBRBRF Input signals
Name
I_A
I_B
I_C
Io
BLOCK
START
POSCLOSE
CB_FAULT
Table 500:
CCBRBRF Output signals
Name
CB_FAULT_AL
TRBU
TRRET
Settings
Values (Range)
Unit
1=on
5=off
0.05...2.00
xIn
0.05...2.00
xIn
1=2 out of 4
2=1 out of 3
3=1 out of 4
1=Current
2=Breaker status
3=Both
1=Off
2=Without Check
3=Current check
0...60000
ms
0...60000
ms
Type
Default
Description
SIGNAL
0
Phase A current
SIGNAL
0
Phase B current
SIGNAL
0
Phase C current
SIGNAL
0
Residual current
BOOLEAN
0=False
Block CBFP operation
BOOLEAN
0=False
CBFP start command
BOOLEAN
0=False
CB in closed position
BOOLEAN
0=False
CB faulty and unable to trip
Type
Description
BOOLEAN
Delayed CB failure alarm
BOOLEAN
Backup trip
BOOLEAN
Retrip
Step
Default
1=on
0.01
0.30
0.01
0.30
2=1 out of 3
1=Current
1=Off
10
120
10
240
1MRS758755 A
Description
Operation Off / On
Operating phase current
Operating residual current
Backup trip current check mode
Operating mode of function
Operating mode of retrip logic
Delay timer for retrip
Delay timer for backup trip
REC615 and RER615
Technical Manual