Section 3
Basic functions
3.16.1.9
128
The function detects the transition from TRUE to FALSE at the CLK input. When the
falling edge is detected, the element assigns the Q output to TRUE. At the next
execution round, the output is returned to FALSE despite the state of the input.
Signals
Table 103:
F_TRIG Input signals
Name
Type
CLK
BOOLEAN
Table 104:
F_TRIG Output signal
Name
Q
Settings
The function does not have any parameters available in LHMI or PCM600.

T_POS_XX function blocks

Function block
GUID-4548B304-1CCD-454F-B819-7BC9F404131F V1 EN
Figure 73:
Function blocks
Functionality
The circuit breaker position information can be communicated with the IEC 61850
GOOSE messages. The position information is a double binary data type which is fed
to the POS input.
T_POS_CL and T_POS_OP are used for extracting the circuit breaker status
information. Respectively, T_POS_OK is used to validate the intermediate or faulty
breaker position.
Table 105:
Cross reference between circuit breaker position and the output of the function block
Circuit breaker position
Output of the function block
T_POS_CL
Intermediate '00'
FALSE
Close '01'
TRUE
Open '10'
FALSE
Faulty '11'
TRUE
Default
0
Type
BOOLEAN
T_POS_OP
FALSE
FALSE
TRUE
TRUE
1MRS758755 A
Description
Input signal
Description
Output signal
T_POS_OK
FALSE
TRUE
TRUE
FALSE
REC615 and RER615
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading