Load Profile Record Ldprlrc; Function Block; Functionality; Quantities - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
3.18
3.18.1
3.18.2
3.18.2.1
REC615 and RER615
Technical Manual

Load profile record LDPRLRC

Function block

GUID-FE70FC2E-8582-4450-97F1-B9D699809951 V1 EN
Figure 109:
Function block

Functionality

The protection relay is provided with a load profile recorder. The load profile feature
stores the historical load data captured at a periodical time interval (demand interval).
Up to 12 load quantities can be selected for recording and storing in a nonvolatile
memory. The value range for the recorded load quantities is about eight times the
nominal value, and values larger than that saturate. The recording time depends on a
settable demand interval parameter and the amount of quantities selected. The record
output is in the COMTRADE format.

Quantities

Selectable quantities are product-dependent.
Table 192:
Quantity Description
Disabled
Quantity not selected
IL1
Phase 1 current
IL2
Phase 2 current
IL3
Phase 3 current
Io
Neutral/earth/residual current
U12
Phase-to-phase 12 voltage
U23
Phase-to-phase 23 voltage
U31
Phase-to-phase 31 voltage
UL1
Phase-to-earth 1 voltage
UL2
Phase-to-earth 2 voltage
UL3
Phase-to-earth 3 voltage
U12B
Phase-to-phase 12 voltage, B side
U23B
Phase-to-phase 23 voltage, B side
U31B
Phase-to-phase 31 voltage, B side
UL1B
Phase-to-earth 1 voltage, B side
UL2B
Phase-to-earth 2 voltage, B side
UL3B
Phase-to-earth 3 voltage, B side
S
Apparent power
Table continues on next page