Monitored Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
Table 658:
SECRSYN Non group settings (Basic)
Parameter
Values (Range)
Operation
Synchro check mode
Dead line value
Live line value
Dead bus value
Live bus value
Max energizing V
Table 659:
SECRSYN Non group settings (Advanced)
Parameter
Values (Range)
Control mode
Close pulse
Phase shift
Minimum Syn time
Maximum Syn time
Energizing time
Closing time of CB
Voltage source switch
9.3.8
REC615 and RER615
Technical Manual
Unit
1=on
5=off
1=Off
2=Synchronous
3=Asynchronous
0.1...0.8
xUn
0.2...1.0
xUn
0.1...0.8
xUn
0.2...1.0
xUn
0.50...1.15
xUn
Unit
1=Continuous
2=Command
200...60000
ms
-180...180
deg
0...60000
ms
100...6000000
ms
100...60000
ms
40...250
ms
0=False
1=True

Monitored data

Table 660:
SECRSYN Monitored data
Name
ENERG_STATE
U_DIFF_MEAS
FR_DIFF_MEAS
PH_DIFF_MEAS
U_DIFF_SYNC
Table continues on next page
Step
Default
1=on
3=Asynchronous
0.1
0.2
0.1
0.8
0.1
0.2
0.1
0.5
0.01
1.05
Step
Default
1=Continuous
10
200
1
0
10
0
10
2000
10
100
10
60
0=False
Type
Values (Range)
Enum
0=Unknown
1=Both Live
2=Live L, Dead B
3=Dead L, Live B
4=Both Dead
FLOAT32
0.00...1.00
FLOAT32
0.000...0.100
FLOAT32
0.00...180.00
BOOLEAN
0=False
1=True
Section 9
Control functions
Description
Operation Off / On
Synchro check operation mode
Voltage low limit line for energizing check
Voltage high limit line for energizing check
Voltage low limit bus for energizing check
Voltage high limit bus for energizing check
Maximum voltage for energizing
Description
Selection of synchro check command or
Continuous control mode
Breaker closing pulse duration
Correction of phase difference between
measured U_BUS and U_LINE
Minimum time to accept synchronizing
Maximum time to accept synchronizing
Time delay for energizing check
Closing time of the breaker
Voltage source switch
Unit
Description
Energization state of Line
and Bus
xUn
Calculated voltage
amplitude difference
xFn
Calculated voltage
frequency difference
deg
Calculated voltage phase
angle difference
Voltage difference out of
limit for synchronizing
629