Monitored Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 8
Measurement functions
Parameter
Zro V Hi high Lim
Zro V High limit
Zro V low limit
Zro V low low Lim
Zro V deadband
8.1.10.5
580
Values (Range)
Unit
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
0.00...4.00
xUn
100...100000

Monitored data

Table 608:
VSMSQI Monitored data
Name
NgSeq-kV
PsSeq-kV
ZroSeq-kV
U2_INST
U2_ANGL
U2_DB
U2_RANGE
U1_INST
U1_ANGL
U1_DB
U1_RANGE
Table continues on next page
Step
Default
1
0.20
1
0.05
1
0.00
1
0.00
1
10000
Type
Values (Range)
FLOAT32
0.00...4.00
FLOAT32
0.00...4.00
FLOAT32
0.00...4.00
FLOAT32
0.00...4.00
FLOAT32
-180.00...180.00
FLOAT32
0.00...4.00
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
FLOAT32
0.00...4.00
FLOAT32
-180.00...180.00
FLOAT32
0.00...4.00
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
1MRS758755 A
Description
High alarm voltage limit for zero sequence
voltage
High warning voltage limit for zero
sequence voltage
Low warning voltage limit for zero
sequence voltage
Low alarm voltage limit for zero sequence
voltage
Deadband configuration value for zero
sequence voltage for integral calculation.
(percentage of difference between min
and max as 0,001 % s)
Unit
Description
xUn
Measured negative
sequence voltage
xUn
Measured positive
sequence voltage
xUn
Measured zero sequence
voltage
xUn
Negative sequence
voltage amplitude,
instantaneous value
deg
Negative sequence
voltage angle
xUn
Negative sequence
voltage amplitude,
reported value
Negative sequence
voltage amplitude range
xUn
Positive sequence
voltage amplitude,
instantaneous value
deg
Positive sequence
voltage angle
xUn
Positive sequence
voltage amplitude,
reported value
Positive sequence
voltage amplitude range
REC615 and RER615
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents