Length Of Record; Uploading Of Record - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 3
Basic functions
3.18.2.2
3.18.2.3
180
Disabled
Quantity not selected
P
Real power
Q
Reactive power
PF
Power factor
If the data source for the selected quantity is removed, for example,
with Application Configuration in PCM600, the load profile recorder
stops recording it and the previously collected data are cleared.

Length of record

The recording capability is about 7.4 years when one quantity is recorded and the
demand interval is set to 180 minutes. The recording time scales down proportionally
when a shorter demand time is selected or more quantities are recorded. The recording
lengths in days with different settings used are presented in
recording buffer is fully occupied, the oldest data are overwritten by the newest data.
Table 193:
Recording capability in days with different settings
1
5
minute
minutes
Amount of
quantities
1
15.2
75.8
2
11.4
56.9
3
9.1
45.5
4
7.6
37.9
5
6.5
32.5
6
5.7
28.4
7
5.1
25.3
8
4.5
22.7
9
4.1
20.7
10
3.8
19.0
11
3.5
17.5
12
3.2
16.2

Uploading of record

The protection relay stores the load profile COMTRADE files to the C:\LDP
\COMTRADE folder. The files can be uploaded with the PCM600 tool or any
appropriate computer software that can access the C:\LDP\COMTRADE folder.
Demand interval
10
15
minutes
minutes
minutes
Recording capability in days
151.6
227.4
454.9
113.7
170.6
341.1
91.0
136.5
272.9
75.8
113.7
227.4
65.0
97.5
194.9
56.9
85.3
170.6
50.5
75.8
151.6
45.5
68.2
136.5
41.4
62.0
124.1
37.9
56.9
113.7
35.0
52.5
105.0
32.5
48.7
97.5
1MRS758755 A
Table
193. When the
30
60
180
minutes
minutes
909.7
2729.2
682.3
2046.9
545.8
1637.5
454.9
1364.6
389.9
1169.6
341.1
1023.4
303.2
909.7
272.9
818.8
248.1
744.3
227.4
682.3
209.9
629.8
194.9
584.8
REC615 and RER615
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents