Technical Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 9
Control functions
9.3.9
9.4
9.4.1
630
Name
Type
PH_DIF_SYNC
BOOLEAN
FR_DIFF_SYNC
BOOLEAN
SECRSYN
Enum

Technical data

Table 661:
SECRSYN Technical data
Characteristic
Operation accuracy
Reset time
Reset ratio
Operate time accuracy in definite time mode
Autoreclosing DARREC
Identification
Function description
Autoreclosing
Values (Range)
Unit
0=False
1=True
0=False
1=True
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the voltage
measured: f
±1 Hz
n
Voltage:
±3.0% of the set value or ±0.01 × U
Frequency:
±10 mHz
Phase angle:
±3°
<50 ms
Typically 0.96
±1.0% of the set value or ±20 ms
IEC 61850
IEC 60617
identification
identification
DARREC
O -> I
1MRS758755 A
Description
Phase angle difference
out of limit for
synchronizing
Frequency difference out
of limit for synchronizing
Status
n
ANSI/IEEE C37.2
device number
79
REC615 and RER615
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents