Settings - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
4.2.3.7
Table 353:
INTRPTEF Group settings (Basic)
Parameter
Values (Range)
Directional mode
Operate delay time
Voltage start value
Table 354:
INTRPTEF Non group settings (Basic)
Parameter
Values (Range)
Operation
Operation mode
Uo signal Sel
Table 355:
INTRPTEF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
Peak counter limit
Min operate current
4.2.3.8
REC615 and RER615
Technical Manual

Settings

Unit
1=Non-directional
2=Forward
3=Reverse
40...1200000
ms
0.05...0.50
xUn
Unit
1=on
5=off
1=Intermittent EF
2=Transient EF
1=Measured Uo
2=Calculated Uo
Unit
40...60000
ms
2...20
0.01...1.00
xIn
Monitored data
Table 356:
INTRPTEF Monitored data
Name
FAULT_DIR
START_DUR
INTRPTEF
Step
Default
2=Forward
10
500
0.01
0.20
Step
Default
1=on
1=Intermittent EF
1=Measured Uo
Step
Default
1
500
1
2
0.01
0.01
Type
Values (Range)
Enum
0=unknown
1=forward
2=backward
3=both
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Section 4
Protection functions
Description
Directional mode
Operate delay time
Voltage start value
Description
Operation Off / On
Operation criteria
Selection for used Uo signal
Description
Reset delay time
Min requirement for peak counter before
start in IEF mode
Minimum operating current for transient
detector
Unit
Description
Detected fault direction
%
Ratio of start time /
operate time
Status
323