Settings - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
9.4.8
Table 669:
DARREC Non group settings (Basic)
Parameter
Values (Range)
Operation
Reclosing operation
Close pulse time
Reclaim time
Terminal priority
Synchronisation set
Auto initiation cnd
Tripping line
Fourth delay in SOTF
First reclose time
Second reclose time
Third reclose time
Fourth reclose time
Fifth reclose time
Table continues on next page
REC615 and RER615
Technical Manual
Table 668:
DARREC Output signals
Name
OPEN_CB
CLOSE_CB
CMD_WAIT
INPRO
LOCKED
PROT_CRD
UNSUC_RECL
AR_ON
READY
ACTIVE

Settings

Unit
1=on
5=off
1=Off
2=External Ctl
3=On
10...10000
ms
100...1800000
ms
1=None
2=Low (follower)
3=High (master)
0...127
1=Not allowed
2=When sync fails
3=CB doesn't close
4=Both
0...63
0=False
1=True
0...300000
ms
0...300000
ms
0...300000
ms
0...300000
ms
0...300000
ms
Type
Description
BOOLEAN
Open command for circuit breaker
BOOLEAN
Close (reclose) command for circuit breaker
BOOLEAN
Wait for master command
BOOLEAN
Reclosing shot in progress, activated during dead
time
BOOLEAN
Signal indicating that AR is locked out
BOOLEAN
A signal for coordination between the AR and the
protection
BOOLEAN
Indicates an unsuccessful reclosing sequence
BOOLEAN
Autoreclosing allowed
BOOLEAN
Indicates that the AR is ready for a new sequence,
i.e. the CB_READY input equals TRUE
BOOLEAN
Reclosing sequence is in progress
Step
Default
1=on
1=Off
10
200
100
10000
1=None
1
0
2=When sync fails
1
0
0=False
10
5000
10
5000
10
5000
10
5000
10
5000
Section 9
Control functions
Description
Operation Off/On
Reclosing operation (Off, External Ctl /
On)
CB close pulse time
Reclaim time
Terminal priority
Selection for synchronizing requirement
for reclosing
Auto initiation condition
Tripping line, defines INIT inputs which
cause OPEN_CB activation
Sets 4th delay into use for all DEL_INIT
signals during SOTF
Dead time for CBB1
Dead time for CBB2
Dead time for CBB3
Dead time for CBB4
Dead time for CBB5
661

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents