1MRS758755 A
6.4.6
6.4.7
Table 552:
PHSVPR Non group settings (Basic)
Parameter
Values (Range)
Operation
Voltage selection
Phase supervision
Table continues on next page
REC615 and RER615
Technical Manual

Signals

Table 550:
PHSVPR Input signals
Name
U_A_AB
U_B_BC
U_C_CA
BLOCK
Table 551:
PHSVPR Output signals
Name
U_LIVE
U_A_AB_LIVE
U_B_BC_LIVE
U_C_CA_LIVE
U_DEAD
U_A_AB_DEAD
U_B_BC_DEAD
U_C_CA_DEAD
Settings
Unit
1=on
5=off
1=phase-to-earth
2=phase-to-phase
1=A or AB
2=B or BC
3=A&B or AB&BC
4=C or CA
5=A&C or AB&CA
6=B&C or BC&CA
7=A&B&C or
AB&BC&CA
Type
Default
Description
SIGNAL
0
Phase-to-earth voltage A or phase-to-phase
voltage AB
SIGNAL
0
Phase-to-earth voltage B or phase-to-phase
voltage BC
SIGNAL
0
Phase-to-earth voltage C or phase-to-phase
voltage CA
BOOLEAN
0=False
Block signal for activating the blocking mode
Type
Description
BOOLEAN
Indicate high voltage presence
BOOLEAN
Indicate high phase to earth voltage A or phase to
phase voltage AB
BOOLEAN
Indicate high phase to earth voltage B or phase to
phase voltage BC
BOOLEAN
Indicate high phase to earth voltage C or phase to
phase voltage CA
BOOLEAN
Indicate low voltage presence
BOOLEAN
Indicate low phase to earth voltage A or phase to
phase voltage AB
BOOLEAN
Indicate low phase to earth voltage B or phase to
phase voltage BC
BOOLEAN
Indicate low phase to earth voltage C or phase to
phase voltage CA
Step
Default
1=on
2=phase-to-phase
4=C or CA
Section 6
Supervision functions
Description
Operation Off / On
Parameter to select phase or phase-to-
phase voltages
Monitored voltage phase
533