Section 3
Basic functions
3.13.4.4
3.13.4.5
Table 51:
RESTVTR Non group settings (Basic)
Parameter
Primary voltage
Secondary voltage
Amplitude Corr
Angle correction
3.13.4.6
3.14
106
The WARNING output in the receiver is activated if the synchronization accuracy of
the sender or the receiver is worse than 4 μs. The output is held on for 10 seconds after
the synchronization accuracy returns within limits.
The WARNING output is always internally active whenever the ALARM output is
active.

Signals

Table 49:
RESTVTR Input signals
Name
Uo
Table 50:
RESTVTR Output signals
Name
ALARM
WARNING

Settings

Values (Range)
Unit
0.100...440.000
kV
60...210
V
0.9000...1.1000
-20.0000...20.0000
deg

Monitored data

Monitored data is available in three locations.
Monitoring/I/O status/Analog inputs
Monitoring/IED status/SMV traffic
Monitoring/IED status/SMV accuracy

GOOSE function blocks

GOOSE function blocks are used for connecting incoming GOOSE data to
application. They support BOOLEAN, Dbpos, Enum, FLOAT32, INT8 and INT32
data types.
Type
Default
INT32-UL0
0
Type
Description
BOOLEAN
Alarm
BOOLEAN
Warning
Step
Default
0.001
11.547
1
100
0.0001
1.0000
0.0001
0.0000
1MRS758755 A
Description
IEC61850-9-2 residual
voltage
Description
Primary voltage
Secondary voltage
Amplitude correction
Angle correction factor
REC615 and RER615
Technical Manual