ABB RELION Series Technical Manual page 643

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

1MRS758755 A
REC615 and RER615
Technical Manual
A070867 V1 EN
Figure 330:
Signal scheme of autoreclosing operation initiated with protection
start signal
The autoreclosing shot is initiated with a start signal of the protection function after the
start delay time has elapsed. The autoreclosing starts when the Str 2 delay shot 1
setting elapses.
A070868 V1 EN
Figure 331:
Signal scheme of autoreclosing operation initiated with protection
operate signal
The autoreclosing shot is initiated with a trip signal of the protection function. The
autoreclosing starts when the protection operate delay time elapses.
Normally, all trip and start signals are used to initiate an autoreclosing shot and trip the
circuit breaker. ACTIVE output indicates reclosing sequence in progress. If any of the
input signals INIT_X or DEL_INIT_X are used for blocking, the corresponding bit
in the Tripping line setting must be FALSE. This is to ensure that the circuit breaker
does not trip from that signal, that is, the signal does not activate the OPEN_CB output.
The default value for the setting is "63", which means that all initiation signals activate
the OPEN_CB output. The lowest bit in the Tripping line setting corresponds to the
INIT_1 input, the highest bit to the INIT_6 line.
Section 9
Control functions
637