Monitored Data - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 4
Protection functions
Table 344:
DEFHPDEF Non group settings (Advanced)
Parameter
Reset delay time
Minimum operate time
Allow Non Dir
Measurement mode
Min operate current
Min operate voltage
Correction angle
Pol reversal
Io signal Sel
Uo signal Sel
Pol quantity
4.2.2.12
312
Values (Range)
Unit
0...60000
ms
40...60000
ms
0=False
1=True
1=RMS
2=DFT
3=Peak-to-Peak
0.005...1.000
xIn
0.01...1.00
xUn
0.0...10.0
deg
0=False
1=True
1=Measured Io
2=Calculated Io
1=Measured Uo
2=Calculated Uo
3=Zero seq. volt.
4=Neg. seq. volt.

Monitored data

Table 345:
DEFLPDEF Monitored data
Name
FAULT_DIR
START_DUR
DIRECTION
ANGLE_RCA
ANGLE
I_OPER
DEFLPDEF
Step
Default
1
20
1
40
0=False
2=DFT
0.001
0.005
0.01
0.01
0.1
0.0
0=False
1=Measured Io
1=Measured Uo
3=Zero seq. volt.
Type
Values (Range)
Enum
0=unknown
1=forward
2=backward
3=both
FLOAT32
0.00...100.00
Enum
0=unknown
1=forward
2=backward
3=both
FLOAT32
-180.00...180.00
FLOAT32
-180.00...180.00
FLOAT32
0.00...40.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
1MRS758755 A
Description
Reset delay time
Minimum operate time for IDMT curves
Allows prot activation as non-dir when dir
info is invalid
Selects used measurement mode
Minimum operating current
Minimum operating voltage
Angle correction
Rotate polarizing quantity
Selection for used Io signal
Selection for used Uo signal
Reference quantity used to determine
fault direction
Unit
Description
Detected fault direction
%
Ratio of start time /
operate time
Direction information
deg
Angle between operating
angle and characteristic
angle
deg
Angle between polarizing
and operating quantity
xIn
Calculated operating
current
Status
REC615 and RER615
Technical Manual