Settings - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 10
Power quality measurement functions
10.3.8
Table 695:
PHQVVR Group settings (Basic)
Parameter
Reference voltage
Voltage dip set 1
VVa dip time 1
Voltage dip set 2
VVa dip time 2
Voltage dip set 3
VVa dip time 3
Voltage swell set 1
VVa swell time 1
Voltage swell set 2
VVa swell time 2
Voltage swell set 3
VVa swell time 3
Voltage Int set
VVa Int time 1
VVa Int time 2
VVa Int time 3
VVa Dur Max
Table 696:
PHQVVR Non group settings (Basic)
Parameter
Operation
Variation enable
Table 697:
PHQVVR Non group settings (Advanced)
Parameter
Phase supervision
Phase mode
694

Settings

Values (Range)
Unit
10.0...200.0
%Un
10.0...100.0
%
0.5...54.0
cycles
10.0...100.0
%
10.0...180.0
cycles
10.0...100.0
%
2000...60000
ms
100.0...140.0
%
0.5...54.0
cycles
100.0...140.0
%
10.0...80.0
cycles
100.0...140.0
%
2000...60000
ms
0.0...100.0
%
0.5...30.0
cycles
10.0...180.0
cycles
2000...60000
ms
100...3600000
ms
Values (Range)
Unit
1=on
5=off
1=Swell
2=Dip
3=Swell + dip
4=Interruption
5=Swell + Int
6=Dip + Int
7=Swell+dip+Int
Values (Range)
Unit
1=Ph A
2=Ph B
3=Ph A + B
4=Ph C
5=Ph A + C
6=Ph B + C
7=Ph A + B + C
1=Three Phase
2=Single Phase
Step
Default
0.1
57.7
0.1
80.0
0.1
3.0
0.1
80.0
0.1
30.0
0.1
80.0
10
3000
0.1
120.0
0.1
0.5
0.1
120.0
0.1
10.0
0.1
120.0
10
2000
0.1
10.0
0.1
3.0
0.1
30.0
10
3000
100
60000
Step
Default
1=on
7=Swell+dip+Int
Step
Default
7=Ph A + B + C
2=Single Phase
1MRS758755 A
Description
Reference supply voltage in %
Dip limit 1 in % of reference voltage
Voltage variation dip duration 1
Dip limit 2 in % of reference voltage
Voltage variation dip duration 2
Dip limit 3 in % of reference voltage
Voltage variation dip duration 3
Swell limit 1 in % of reference voltage
Voltage variation swell duration 1
Swell limit 2 in % of reference voltage
Voltage variation swell duration 2
Swell limit 3 in % of reference voltage
Voltage variation swell duration 3
Interruption limit in % of reference voltage
Voltage variation Int duration 1
Voltage variation Int duration 2
Voltage variation interruption duration 3
Maximum voltage variation duration
Description
Operation Off / On
Enable variation type
Description
Monitored voltage phase
Three/Single phase mode
REC615 and RER615
Technical Manual