Section 9
Control functions
9.5.7
Table 678:
ATSABTC Non group settings (Basic)
Parameter
Operation
Main bus priority
Operate delay CB tr
Transfer dead time
Reconnection delay
9.5.8
9.5.9
672
Table 677:
ATSABTC Output signals
Name
OPEN_CB1
CLOSE_CB1
OPEN_CB2
CLOSE_CB2
INPRO
BLKD_AL

Settings

Values (Range)
Unit
1=on
5=off
1=Bus 1
2=Bus 2
0...120000
ms
0...120000
ms
0...300000
ms
Monitored data
Table 679:
ATSABTC Monitored data
Name
ATSABTC
Technical data
Table 680:
ATSABTC Technical data
Characteristic
Operation time accuracy
Type
Description
BOOLEAN
Circuit breaker open command for bus 1
BOOLEAN
Circuit breaker close command for bus 1
BOOLEAN
Circuit breaker open command for bus 2
BOOLEAN
Circuit breaker close command for bus 2
BOOLEAN
Automatic operation in progress
BOOLEAN
Automatic transfer switch blocked alarm
Step
Default
1=on
1=Bus 1
10
200
10
100
10
60000
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
±1.0% of the set value or ±20 ms
1MRS758755 A
Description
Operation Off / On
Main bus priority (1 or 2)
Circuit breaker trip delay
Transfer dead time for closing of circuit
breaker
Delay for opening of non prioritized CB
Unit
Description
Status
REC615 and RER615
Technical Manual