Section 4
Protection functions
4.2.1.6
266
Table 284:
Measurement modes supported by (F)EFxPTOC stages
Measurement mode
FEFLPTOC
RMS
DFT
Peak-to-Peak
For a detailed description of the measurement modes, see the
Measurement modes

Timer characteristics

(F)EFxPTOC supports both DT and IDMT characteristics. The user can select the
timer characteristics with the Operating curve type and Type of reset curve settings.
When the DT characteristic is selected, it is only affected by the Operate delay time
and Reset delay time settings.
The protection relay provides 55 IDMT characteristics curves, of which seven comply
with the IEEE C37.112 and six with the IEC 60255-3 standard. Two curves follow the
special characteristics of ABB praxis and are referred to as RI and RD. One user
programmable curve can be used if none of the standard curves are applicable. In
addition to this, there are 39 curves for recloser applications. The user can choose the
DT characteristic by selecting the Operating curve type values "ANSI Def. Time" or
"IEC Def. Time". The functionality is identical in both cases.
The following characteristics, which comply with the list in the IEC 61850-7-4
specification, indicate the characteristics supported by different stages:
Table 285:
Timer characteristics supported by different stages
Operating curve type
(1) ANSI Extremely Inverse
(2) ANSI Very Inverse
(3) ANSI Normal Inverse
(4) ANSI Moderately Inverse
(5) ANSI Definite Time
(6) Long Time Extremely Inverse
(7) Long Time Very Inverse
(8) Long Time Inverse
(9) IEC Normal Inverse
(10) IEC Very Inverse
(11) IEC Inverse
(12) IEC Extremely Inverse
(13) IEC Short Time Inverse
Table continues on next page
EFHPTOC
x
x
x
x
x
x
section in this manual.
(F)EFLPTOC
x
x
x
x
x
x
x
x
x
x
x
x
x
1MRS758755 A
EFIPTOC
x
EFHPTOC
x
x
x
x
x
x
REC615 and RER615