Binary Input Inversion - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 3
Basic functions
3.10.2
80
1
3
4
GUID-13DA5833-D263-4E23-B666-CF38B1011A4B V1 EN
Figure 25:
Binary input filtering
1 t
0
2 t
1
3 Input signal
4 Filtered input signal
5 Filter time
At the beginning, the input signal is at the high state, the short low state is filtered and
no input state change is detected. The low state starting from the time t
filter time, which means that the change in the input state is detected and the time tag
attached to the input change is t
time tag t
is attached.
1
Each binary input has a filter time parameter "Input # filter", where # is the number of
the binary input of the module in question (for example "Input 1 filter").
Table 32:
Input filter parameter values
Parameter
Input # filter time

Binary input inversion

The parameter Input # invert is used to invert a binary input.
Table 33:
Binary input states
Control voltage
No
Yes
No
Yes
2
5
5
. The high state starting from t
0
Values
5...1000 ms
Input # invert
0
0
1
1
1MRS758755 A
exceeds the
0
is detected and the
1
Default
5 ms
State of binary input
FALSE (0)
TRUE (1)
TRUE (1)
FALSE (0)
REC615 and RER615
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents