Section 3
Basic functions
3.16.10.3
3.16.10.4
Table 162:
SCA4GAPC Non group settings (Basic)
Parameter
Scale ratio 1
Scale ratio 2
Scale ratio 3
Scale ratio 4
152
Analog output range is from -2000000.0 to 2000000.0.
If the value of the AIn_VALUE input exceeds the analog input range,
AOn_VALUE is set to 0.0.
If the result of AIn_VALUE multiplied by the Scale ratio n setting
exceeds the analog output range, AOn_VALUE shows the minimum or
maximum value, according to analog value range.

Signals

Table 160:
SCA4GAPC Input signals
Name
AI1_VALUE
AI2_VALUE
AI3_VALUE
AI4_VALUE
Table 161:
SCA4GAPC Output signals
Name
AO1_VALUE
AO2_VALUE
AO3_VALUE
AO4_VALUE

Settings

Values (Range)
Unit
0.001...1000.000
0.001...1000.000
0.001...1000.000
0.001...1000.000
Type
Default
Description
FLOAT32
0.0
Analog input value of channel 1
FLOAT32
0.0
Analog input value of channel 2
FLOAT32
0.0
Analog input value of channel 3
FLOAT32
0.0
Analog input value of channel 4
Type
Description
FLOAT32
Analog value 1 after scaling
FLOAT32
Analog value 2 after scaling
FLOAT32
Analog value 3 after scaling
FLOAT32
Analog value 4 after scaling
Step
Default
0.001
1.000
0.001
1.000
0.001
1.000
0.001
1.000
1MRS758755 A
Description
Scale ratio for analog value 1
Scale ratio for analog value 2
Scale ratio for analog value 3
Scale ratio for analog value 4
REC615 and RER615
Technical Manual