the set Start value df/dt value, the module reports the exceeding of the value to the
operate logic module.
The protection relay does not accept the set value "0.00" for the Start
value df/dt setting.
Operate logic
This module is used for combining different protection criteria based on the frequency
and the frequency gradient measurement to achieve a more sophisticated behavior of
the function. The criteria are selected with the Operation mode setting.
Table 457:
Operation modes for operation logic
Operation mode
Freq<
Freq>
df/dt
Table continues on next page
Description
The function operates independently as the underfrequency
("Freq<") protection function. When the measured frequency is
Start value Freq< setting, the module
below the set value of the
activates the START and STR_UFRQ outputs. The time characteristic
is according to DT. When the operation timer has reached the value
set by the
Operate Tm Freq setting, the OPERATE and OPR_UFRQ
outputs are activated. If the frequency restores before the module
operates, the reset timer is activated. If the timer reaches the value
Reset delay Tm Freq setting, the operate timer resets and
set by the
the START and STR_UFRQ outputs are deactivated.
The function operates independently as the overfrequency
("Freq>") protection function. When the measured frequency
exceeds the set value of the
activates the START and STR_OFRQ outputs. The time characteristic
is according to DT. When the operation timer has reached the value
Operate Tm Freq setting, the OPERATE and OPR_OFRQ
set by the
outputs are activated. If the frequency restores before the module
operates, the reset timer is activated. If the timer reaches the value
Reset delay Tm Freq setting, the operate timer resets and
set by the
the START and STR_OFRQ outputs are deactivated.
The function operates independently as the frequency gradient ("df/
dt"), rate-of-change, protection function. When the frequency
gradient exceeds the set value of the
module activates the START and STR_FRG outputs. The time
characteristic is according to DT. When the operation timer has
Operate Tm df/dt setting, the OPERATE
reached the value set by the
and OPR_FRG outputs are activated. If the frequency gradient
restores before the module operates, the reset timer is activated. If
the timer reaches the value set by the
the operate timer resets and the START and STR_FRG outputs are
deactivated.
Section 4
Protection functions
Start value Freq> setting, the module
Start value df/dt setting, the
Reset delay Tm df/dt setting,