Function Block - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 8
Measurement functions
8.1.7.2
8.1.7.3
8.1.7.4
Table 590:
RESVMMXU Non group settings (Basic)
Parameter
Operation
V Hi high limit res
V high limit res
V deadband res
Table 591:
RESVMMXU Non group settings (Advanced)
Parameter
Measurement mode
572

Function block

A070779 V2 EN
Figure 298:
Function block
Signals
Table 588:
RESVMMXU Input signals
Name
Uo
BLOCK
Table 589:
RESVMMXU Output signals
Name
HIGH_ALARM
HIGH_WARN
Settings
Values (Range)
Unit
1=on
5=off
0.00...4.00
xUn
0.00...4.00
xUn
100...100000
Values (Range)
Unit
1=RMS
2=DFT
Type
Default
Description
SIGNAL
0
Residual voltage
BOOLEAN
0=False
Block signal for all binary outputs
Type
Description
BOOLEAN
High alarm
BOOLEAN
High warning
Step
Default
1=on
1
0.20
1
0.05
1
10000
Step
Default
2=DFT
1MRS758755 A
Description
Operation Off / On
High alarm voltage limit
High warning voltage limit
Deadband configuration value for integral
calculation. (percentage of difference
between min and max as 0,001 % s)
Description
Selects used measurement mode
REC615 and RER615
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rer615Rec615

Table of Contents