Calibration; Limit Value Supervision - ABB RELION Series Technical Manual

Grid automation
Hide thumbs Also See for RELION Series:
Table of Contents

Advertisement

Section 3
Basic functions
3.12.2.6
3.12.2.7
90
are sampled. Each RTD sensor type has expected current based on the sensor type. If
the measured offset current deviates from the reference current more than 20%, the
sample is discarded and the output is set to invalid. The invalid measure status
deactivates as soon as the measured input signal is within the measurement offset.

Calibration

RTD and mA inputs are calibrated at the factory. The calibration circuitry monitors
the RTD channels continuously and reports a circuitry break of any channel.

Limit value supervision

The limit value supervision function indicates whether the measured value of
AI_INST# exceeds or falls below the set limits. All the measuring channels have an
individual limit value supervision function. The measured value contains the
corresponding range information AI_RANGE# and has a value in the range of 0 to 4:
0: "normal"
1: "high"
2: "low"
3: "high-high"
4: "low-low"
The range information changes and the new values are reported.
Y
Value maximum
Val high high limit
Val high limit
AI_RANGE#=0
Val low limit
AI_RANGE#=2
Val low low limit
AI_RANGE#=4
Value minimum
GUID-6A6033E6-22C8-415D-AABD-D0556D38C986 V1 EN
Figure 34:
Limit value supervision for RTD (X130)
The range information of "High-high limit" and "Low-low limit" is combined from all
measurement channels to the Boolean ALARM output. The range information of
"High limit" and "Low limit" is combined from all measurement channels to the
Boolean WARNING output.
Out of Range
AI_RANGE#=3
Hysteresis
AI_RANGE#=1
AI_RANGE#=0
1MRS758755 A
t
Value Reported
REC615 and RER615
Technical Manual